Platinum Series UPS 1Ph 1-3kVA

True On-line Double Conversion Platinum Series UPS Series has been designed to support and protect various applications. Ideal backup system for VolP, PBX systems, Telecom systems, small data centers and advanced control systems.

Category:

UPS Brochure
1-1.5kVA UPS Drawing
2kVA UPS Drawing
3kVA UPS Drawing
UPS Install / Operation Manual
Bypass Switch Drawing
SNMP-UPS-quick-guide-20130118
Modbus-manual-20200902
AS400+software1-quickguide-v4-20170330
Platinum UPS Series Battery Backup Time Run Chart 1kVA and 1.5kVA
Platinum UPS Series Battery Backup Time Run Chart 2kVA and 3kVA

Features

  • Extended Battery Cabinets:  All Platinum Series units are supported with additional battery backup by using the extended battery cabinets. Extended battery cabinets are optional and allow users to have extended run-times dependent on requirements.
  • Communication Cards:  Available communication cards include the following: Standard SNMP Protocol, MODBUS Communication and WiFi Communication.
  • Conformal Coated Boards:  Conformal coated boards allows for the Platinum Series to be used in “light industrial” applications. Boards that are conformal coated include the Main PCB, Communication Card, Charger, and Control boards.
  • Warranty:  Platinum series comes with a two year warranty on the electronics, one year warranty on the batteries. For additional warranty options please contact the factory.

Specifications

MODEL PLATINUM SERIES UPS
1kVA 1.5kVA 2kVA 3kVA
Capacity 1kVA / 1kW 1.5kVA / 1.5kW 2kVA / 2kW 3kVA / 3kW
INPUT
Input Voltage (range) 90-150VAC
Phase 1 Phase
Frequency Range 50/60Hz +/-4%
Power Factor ≧ 0.95 at 100% Load
Input THD <9.0%
OUTPUT
Output Voltage 100/110/115/120VAC
Phase 1 Phase
Frequency Sync Range 46Hz ~ 54Hz @ 50Hz System, 56Hz ~ 64Hz @ 60Hz System, (Batt Mode) +/- 0.1% Hz
Output THD ≦ 2% at 100% Linear Load / ≦ 4% at 100% Non-linear Load (PF≥0.8)
Voltage Regulation ± 1%
Overload – AC Mode 100%~110% for 1hr / 110-130% for 1min / >130%: 1sec
Overload – Battery Mode 100-110%: 30sec / 110-130%: 10sec / >130%: 1sec
Current Crest Ratio 3:1 Max
EFFICIENCY
AC Mode 84 – 86%
BATTERY
Battery Voltage 36VDC 72VDC
Battery Backup Time @ 3.5 minutes at full load
Charger Current 1.0A
Recharge Time 7 hours at 90%
Internal Batteries 3 x 9AH 3 x 9AH 6 x 7AH 6 x 9AH
PHYSICAL
Dimensions WxDxH 17.25″W x 16.15″D x 3.40″H 17.25″W x 24.80″D x 3.40″H
Weight (lbs) 37 37 83 83
ENVIRONMENT
Operating Temperature 0-40°C (the battery life will decrease when > 25°C)
Operating Humidity <95% non-condensing
Operating Altitude ft (m) 2,000ft
Heat Dissipation (BTU/Hr) 520 877 1171 1500
Acoustic Noise Level 55-60dB at 1 meter
COMMUNICATION
RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
MODBUS Card Power Management with MODBUS communication
Optional SNMP Power management from SNMP manager and web browser
AGENCY APPROVAL
Safety UL 1778 / IEC 61000-4-3
Environmental FCC Part 15J, Class A